(021) 612 3131 / 0812 9726 3131 cs@apc-indonesia.com

Galaxy VS UPS 30kW 400V for up to 4 internal 9Ah

smart modular battery strings, Start-up 5×8 (GVSUPS30K0B4HS)

Gambar UPS APC Galaxy VS Three Phase 30kW 400V (GVSUPS30K0B4HS)

 

Specifications UPS APC Three Phase (GVSUPS30K0B4HS)

Overview
– Presentation : Highly efficient, easy-to-deploy 30kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 4 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5×8 start-up service.
– Lead time : Usually Ships within 2 Weeks

Main
– Main Input Voltage : 400 V 3 phases
– Other Input Voltage : 380 V, 415 V
– Main Output Voltage : 400 V 3 phases
– Other Output Voltage : 380 V, 415 V
– rated power in W : 30 kW
– Rated power in VA : 30 kVA
– Battery type : Internal modular battery VRLA
– Provided equipment :
> Dust filter
> Installation manual
> Integrated network management
> Start-up service
> EcoStruxure Ready

General
– Redundant : No

Physical
– Colour : White
– Height : 148.5 cm
– Width : 52.1 cm
– Depth : 84.7 cm
– Net weight : 200 kg
– USB compatible : No

Input
– Network frequency : 40…70 Hz
– Input voltage limits : 340…460 V 400 V
– Maximum input current : 54 A
– Max short time withstand current : 65 kA
– Input harmonic distortion : Less than 3 % for full load
– Load power factor : From 0.7 leading to 0.7 lagging without any derating
– Input Power Factor at Full Load : 0.99

Output
– Maximum configurable power in W : 30 kW
– Harmonic distortion : Less than 3 %
– Output frequency : 50 Hz sync to mains, 60 Hz sync to mains
– Crest factor : 2.5
– Wave type : Sine wave
– Output voltage tolerance : +/- 5% after 2ms, +/-1% after 50ms
– Output harmonic distortion : < 1% linear load and < 3% non-linear load
– Output overload operation : 10 minutes at 125% and 60 seconds at 150%
– bypass type : Built-in static bypass
– Maximum configurable power in VA : 30 kVA

Conformance
– Standards : IEC 62040-1-1, IEC 62040-2, OSHPD

Environmental
– Ambient air temperature for operation : 0…40 °C
– Relative humidity : 0…95 % non-condensing
– Operating altitude : 0…3300 ft
– Ambient air temperature for storage : -15…40 °C
– Storage Relative Humidity : 10…80 % non-condensing
– Storage altitude : 0.00…3048.00 m
– Acoustic level : 61 dBA
– heat dissipation : 3395 Btu/h
– IP degree of protection : IP20

Batteries & Runtime
– Efficiency : View Efficiency Graph
– Battery voltage : 480 V
– Discharge battery voltage : 384 V
– Max current discharge : 81 A
– Battery power in VAH : 0 VAh runtime
– Extended runtime : 0

Communications & Management
– control panel : Touch screen LCD user interface

Packing Units
– Unit Type of Package 1 : PCE
– Number of Units in Package 1 : 1
– Package 1 Height : 168 cm
– Package 1 Width : 99 cm
– Package 1 Length : 64 cm
– Package 1 Weight : 200 kg

Contractual warranty
– Warranty : 1 year on-site repair or replace with factory authorized Start-Up